What Are D1 and D2 Discharge Pipes?
Every unvented hot water storage cylinder installed in the UK must be equipped with a temperature and pressure relief valve (TPRV) and, in most installations, a temperature relief valve (TRV) as independent safety devices. Under abnormal conditions β including thermostat failure, loss of cold feed, or immersion heater runaway β these valves open automatically to discharge dangerously hot water and relieve system pressure before a catastrophic failure can occur.
The pipework through which this discharged water is safely conveyed away from the cylinder is divided into two distinct sections, referred to in the Building Regulations as D1 and D2, with a tundish forming the critical visible air break between them.
D1 Pipework β The Short Discharge Connection
The D1 pipe is the section of discharge pipework that runs from the outlet of the temperature relief valve (or combined temperature and pressure relief valve) directly down to the inlet of the tundish. Building Regulations and the manufacturer's installation instructions impose strict constraints on D1 pipework:
The Tundish β Visible Air Break
The tundish is a funnel-like fitting that creates an air break between the D1 pipe and the D2 pipe. This visible air break serves two critical purposes. First, it provides an observable indication that a relief valve has operated β a building occupant or engineer can see water dripping or flowing through the tundish and understand that an abnormal condition has occurred. Second, the air break prevents any back-pressure from the D2 discharge pipe acting against the relief valve, which could prevent the valve from closing properly after the discharge event.
The tundish must be positioned in a visible location β typically in the airing cupboard, plant room, or cupboard housing the cylinder β and must not be concealed behind panels or in locations inaccessible without tools.
D2 Pipework β The Long Discharge Run
The D2 pipe runs from the outlet of the tundish to the final discharge termination point. It is the section of discharge pipework that presents the most significant design challenge, as it must typically traverse considerable distances through the building fabric before reaching a safe external or compliant internal termination point. The sizing and routing of D2 pipework is the primary purpose of this calculator.
G3 Building Regulations β Discharge Requirements
Key G3 Discharge Requirements
| Requirement | D1 Pipe | Tundish | D2 Pipe |
|---|---|---|---|
| Material | Metal only (copper) | Any approved material | Metal or approved plastic (high-temp rated) |
| Maximum length | 600mm | N/A | See sizing table (diameter dependent) |
| Minimum size | Same as valve outlet | Suitable for D1 bore | One size larger than D1 minimum |
| Fall required | Vertical/near-vertical | N/A | Continuous fall min 1:200 |
| Visibility | Not required | Must be visible | Termination must be visible |
| Air break | N/A | Air break to D2 | Not required (after tundish) |
| Insulation | Not required | Not required | Freeze protection in exposed sections |
| Bends permitted | None preferred | N/A | Yes, with equivalent length allowance |
Approved Persons and Certification
Unvented hot water cylinder installations must be carried out by a G3-competent installer β a person who holds a current qualification (such as City & Guilds 6189, ACS G3 assessment, or BPEC equivalent) and is registered with an Approved Inspector or a Competent Persons Scheme such as APHC, NAPIT, or Gas Safe (for combination systems).
The installer must issue a Building Regulations compliance certificate (notification to the local authority) upon completion. Non-compliant discharge pipework β including undersized D2 pipe, blocked tundish, or inappropriate termination β constitutes a breach of Building Regulations and is a notifiable defect that must be rectified.
D1 and D2 Pipe Sizing Rules
The pipe sizing rules for D2 discharge pipework are derived from the Approved Document G guidance tables, which in turn are based on hydraulic calculations of the discharge flow rates expected from temperature and pressure relief valves at their rated conditions. The fundamental rule is that the D2 pipe must have adequate bore to convey the maximum rated discharge flow of the relief valve to atmosphere without causing back-pressure at the tundish.
The Step-Up Rule β Minimum D2 Size
The absolute minimum requirement is that D2 must be at least one pipe size larger than D1 (the tundish outlet). In standard domestic installations:
| D1 (Tundish Outlet) | Min D2 Pipe Size | Max D2 Length (Copper) | Max D2 Length (Plastic) |
|---|---|---|---|
| 15mm | 22mm minimum | 9.0m equivalent | 9.0m equivalent |
| 15mm | 28mm (if 22mm insufficient) | 18.0m equivalent | 18.0m equivalent |
| 22mm | 28mm minimum | 18.0m equivalent | 18.0m equivalent |
| 22mm | 35mm (if 28mm insufficient) | 27.0m equivalent | 27.0m equivalent |
| 28mm | 35mm minimum | 27.0m equivalent | 27.0m equivalent |
Equivalent Length Calculation
The maximum permitted D2 pipe length is not simply the measured physical length β it is the total equivalent length, which accounts for the hydraulic resistance of bends and fittings in addition to the straight pipe run. Each bend or elbow in a D2 pipe run adds a penalty equivalent length that reduces the remaining allowable straight-pipe distance.
| Pipe Size | Standard 90Β° Elbow | 45Β° Elbow | Long-Radius 90Β° Bend | Tee (straight through) |
|---|---|---|---|---|
| 22mm | 0.8m | 0.4m | 0.5m | 0.3m |
| 28mm | 1.0m | 0.5m | 0.6m | 0.4m |
| 35mm | 1.4m | 0.7m | 0.9m | 0.6m |
| 42mm | 1.7m | 0.9m | 1.1m | 0.7m |
Worked Equivalent Length Formula
Where L_straight = measured pipe length in metres, n = number of each fitting type, K = equivalent length penalty from the table above.
D2 Discharge Pipe Sizing Tables β Full Reference
| Scenario | D1 Size | D2 Size | Max Equiv. Length | Max 90Β° Elbows (std) | Compliance |
|---|---|---|---|---|---|
| Short domestic run | 15mm | 22mm | 9.0m | 11 max | β Compliant |
| Medium domestic run | 15mm | 28mm | 18.0m | 18 max | β Compliant |
| Long domestic run | 15mm | 35mm | 27.0m | 19 max | β Compliant |
| Commercial short | 22mm | 28mm | 18.0m | 18 max | β Compliant |
| Commercial medium | 22mm | 35mm | 27.0m | 19 max | β Compliant |
| Undersized β common error | 15mm | 15mm | N/A | N/A | β Non-compliant |
| Same size β not permitted | 22mm | 22mm | N/A | N/A | β Non-compliant |
| Property | Copper (BS EN 1057) | CPVC / HT Plastic | Stainless Steel |
|---|---|---|---|
| Max service temp | β₯ 95Β°C (unlimited) | 95Β°C (check mfr) | β₯ 95Β°C |
| Permitted for D1 | β Yes | β No | β Yes |
| Permitted for D2 | β Yes | β If approved | β Yes |
| Absolute roughness Ξ΅ | 0.0015mm (smooth) | 0.0015mm (smooth) | 0.015β0.025mm |
| Bore equivalence | Standard | Standard | Standard |
| Freeze susceptibility | Risk in exposed runs | Risk in exposed runs | Risk in exposed runs |
| Max length (22mm) | 9.0m equivalent | 9.0m equivalent | 9.0m equivalent |
| Max length (28mm) | 18.0m equivalent | 18.0m equivalent | 18.0m equivalent |
D2 Discharge Pipe Termination Requirements
The termination point of the D2 pipe is as important as its sizing. A correctly sized D2 pipe that terminates inappropriately remains non-compliant. Approved Document G sets out specific requirements for where and how D2 pipework must terminate.
Approved Termination Locations
Termination Visibility Requirement
The G3 visibility requirement means the discharge point β whether the tundish in the airing cupboard or the D2 termination point externally β must be observable without using tools or moving fixed objects. The purpose is to alert occupants that a safety device has operated and that the system requires inspection by a competent engineer. Where the D2 runs a long distance, a secondary visible indicator (such as a sight glass or second tundish) can be used.
Worked Calculation Examples
Example 1: Standard 210L Domestic Cylinder β Short Run
Scenario: 210 litre unvented cylinder, 15mm TPRV outlet, tundish in airing cupboard, D2 runs 4.2m through ceiling void and exits through external wall. Two 90Β° standard elbows (22mm) in D2 run.
Determine D1 Size
TPRV outlet = 15mm. D1 pipe = 15mm copper. Length of D1 = 420mm (within 600mm limit). β
Determine Minimum D2 Size
D1 is 15mm β D2 minimum = 22mm (one size up). Start with 22mm D2.
Calculate Total Equivalent Length
Check Against Maximum
Verify Continuous Fall
D2 run must maintain minimum 1:200 fall (5mm per metre). Over 4.2m pipe run, minimum total fall = 21mm. Confirm with installer. Termination over trapped gully at external wall low level. β
Example 2: Long D2 Run β Multiple Bends
Scenario: 300L commercial unvented cylinder, 15mm D1, D2 must run 12m through service corridor with four 90Β° standard elbows (28mm).
Start with 22mm D2 (minimum)
Try 28mm D2
Final Specification
Use 28mm D2 copper pipe throughout. Verify 1:200 continuous fall (60mm over 12m). Terminate over trapped gully at visible, accessible external location.
Example 3: Plastic D2 Pipe β Apartment Installation
Scenario: 170L unvented cylinder in flat, 15mm D1, D2 must discharge internally into floor drain. 6.5m run, one 90Β° elbow, one 45Β° elbow (22mm fittings). Plastic pipe (manufacturer-approved, temperature rated).
Confirm Plastic is Acceptable
Check cylinder manufacturer's documentation β plastic (CPVC/HT-rated) approved for D2 in this model. D1 remains 15mm copper. β
Calculate Equivalent Length at 22mm
Termination
Discharge to floor drain with visible air gap (minimum 20mm above drain grating). Tundish in accessible airing cupboard acts as primary visible indicator. β
Common D2 Discharge Pipe Installation Mistakes
These are the most frequently encountered non-compliant discharge pipe installations identified during G3 inspection and remedial surveys: