Unvented Cylinder Discharge Pipe Size Calculator

Unvented Cylinder Discharge Pipe Size Calculator

Determine the correct D2 discharge pipe diameter for unvented hot water cylinders based on pipe length and fittings, in line with UK Part G guidance.

Discharge Pipe Recommendation

UK Standard: D2 discharge pipes must be sized correctly to safely carry hot water/steam from the TPRV and must not reduce in diameter.
⚠️ Safety Notice: Unvented hot water systems must be installed and maintained by qualified, G3-certified engineers only.
Β© 2026 Unvented Cylinder Discharge Pipe Size Calculator
Unvented Cylinder Discharge Pipe Size Calculator | D1 & D2 Pipe Sizing | G3 Regulations | AnglianPHE
Building Regulations Β· Approved Document G Β· Section G3

Unvented Cylinder Discharge Pipe
Size Calculator

Calculate D2 discharge pipe sizes for unvented hot water cylinders in compliance with G3 Building Regulations. Covers D1/D2 pipework, equivalent length, bend penalties, and termination requirements β€” for G3-qualified engineers, heating contractors, and mechanical services designers.

Approved Document G3
BS EN 12897
Gas Safe / APHC
D1 & D2 Pipe Sizing

What Are D1 and D2 Discharge Pipes?

Every unvented hot water storage cylinder installed in the UK must be equipped with a temperature and pressure relief valve (TPRV) and, in most installations, a temperature relief valve (TRV) as independent safety devices. Under abnormal conditions β€” including thermostat failure, loss of cold feed, or immersion heater runaway β€” these valves open automatically to discharge dangerously hot water and relieve system pressure before a catastrophic failure can occur.

The pipework through which this discharged water is safely conveyed away from the cylinder is divided into two distinct sections, referred to in the Building Regulations as D1 and D2, with a tundish forming the critical visible air break between them.

D1 / Tundish / D2 Schematic β€” Unvented Cylinder Discharge System
UNVENTED CYLINDER TPRV D1 max 600mm metal only TUNDISH ← air gap visible break D2 DISCHARGE PIPE min 1:200 fall throughout TRAPPED GULLY TERMINATION D1: same size as valve outlet (typ. 15mm) D2: minimum one pipe size larger than D1 (typ. 22mm min)

D1 Pipework β€” The Short Discharge Connection

The D1 pipe is the section of discharge pipework that runs from the outlet of the temperature relief valve (or combined temperature and pressure relief valve) directly down to the inlet of the tundish. Building Regulations and the manufacturer's installation instructions impose strict constraints on D1 pipework:

Maximum Length: 600mm
D1 must be as short as practical. The absolute maximum permitted length from valve outlet to tundish is 600mm. Longer runs risk condensation, valve corrosion, and thermal shock issues.
Metal Pipe Only
D1 must be constructed from metal pipe β€” typically 15mm copper tube. Plastic pipe is not permitted for D1 due to the high temperatures (up to 95Β°C) discharged directly from the valve.
Vertical or Near-Vertical
D1 should run vertically downward or as close to vertical as the installation allows. This ensures gravity discharge and prevents water pooling at the valve outlet, which could impair operation.
Same Diameter as Valve Outlet
The D1 pipe bore must match the outlet size of the relief valve β€” typically 15mm for domestic installations. Do not reduce the bore of D1 at any point.

The Tundish β€” Visible Air Break

The tundish is a funnel-like fitting that creates an air break between the D1 pipe and the D2 pipe. This visible air break serves two critical purposes. First, it provides an observable indication that a relief valve has operated β€” a building occupant or engineer can see water dripping or flowing through the tundish and understand that an abnormal condition has occurred. Second, the air break prevents any back-pressure from the D2 discharge pipe acting against the relief valve, which could prevent the valve from closing properly after the discharge event.

The tundish must be positioned in a visible location β€” typically in the airing cupboard, plant room, or cupboard housing the cylinder β€” and must not be concealed behind panels or in locations inaccessible without tools.

D2 Pipework β€” The Long Discharge Run

The D2 pipe runs from the outlet of the tundish to the final discharge termination point. It is the section of discharge pipework that presents the most significant design challenge, as it must typically traverse considerable distances through the building fabric before reaching a safe external or compliant internal termination point. The sizing and routing of D2 pipework is the primary purpose of this calculator.

G3 Building Regulations β€” Discharge Requirements

Legal requirement: Building Regulations Approved Document G, Requirement G3 states that a hot water storage system with a capacity greater than 15 litres, or operating at pressure greater than 0.5 bar, must incorporate safety devices that, if operated, discharge in a safe manner. All unvented hot water cylinders above 15 litres fall within this scope. Installation must be carried out by a competent person registered with a Competent Persons Scheme (CPS).

Key G3 Discharge Requirements

Building Regulations Part G3 β€” Discharge Pipe Requirements Summary
RequirementD1 PipeTundishD2 Pipe
MaterialMetal only (copper)Any approved materialMetal or approved plastic (high-temp rated)
Maximum length600mmN/ASee sizing table (diameter dependent)
Minimum sizeSame as valve outletSuitable for D1 boreOne size larger than D1 minimum
Fall requiredVertical/near-verticalN/AContinuous fall min 1:200
VisibilityNot requiredMust be visibleTermination must be visible
Air breakN/AAir break to D2Not required (after tundish)
InsulationNot requiredNot requiredFreeze protection in exposed sections
Bends permittedNone preferredN/AYes, with equivalent length allowance

Approved Persons and Certification

Unvented hot water cylinder installations must be carried out by a G3-competent installer β€” a person who holds a current qualification (such as City & Guilds 6189, ACS G3 assessment, or BPEC equivalent) and is registered with an Approved Inspector or a Competent Persons Scheme such as APHC, NAPIT, or Gas Safe (for combination systems).

The installer must issue a Building Regulations compliance certificate (notification to the local authority) upon completion. Non-compliant discharge pipework β€” including undersized D2 pipe, blocked tundish, or inappropriate termination β€” constitutes a breach of Building Regulations and is a notifiable defect that must be rectified.

Certification note: AnglianPHE engineers are NAPIT-approved and G3-qualified. All unvented cylinder installations include Building Regulations compliance notification and a full commissioning record.

D1 and D2 Pipe Sizing Rules

The pipe sizing rules for D2 discharge pipework are derived from the Approved Document G guidance tables, which in turn are based on hydraulic calculations of the discharge flow rates expected from temperature and pressure relief valves at their rated conditions. The fundamental rule is that the D2 pipe must have adequate bore to convey the maximum rated discharge flow of the relief valve to atmosphere without causing back-pressure at the tundish.

The Step-Up Rule β€” Minimum D2 Size

The absolute minimum requirement is that D2 must be at least one pipe size larger than D1 (the tundish outlet). In standard domestic installations:

Minimum D2 Pipe Size Based on D1 (Tundish Outlet) Size
D1 (Tundish Outlet)Min D2 Pipe SizeMax D2 Length (Copper)Max D2 Length (Plastic)
15mm22mm minimum9.0m equivalent9.0m equivalent
15mm28mm (if 22mm insufficient)18.0m equivalent18.0m equivalent
22mm28mm minimum18.0m equivalent18.0m equivalent
22mm35mm (if 28mm insufficient)27.0m equivalent27.0m equivalent
28mm35mm minimum27.0m equivalent27.0m equivalent

Equivalent Length Calculation

The maximum permitted D2 pipe length is not simply the measured physical length β€” it is the total equivalent length, which accounts for the hydraulic resistance of bends and fittings in addition to the straight pipe run. Each bend or elbow in a D2 pipe run adds a penalty equivalent length that reduces the remaining allowable straight-pipe distance.

Equivalent Length Penalties for Bends and Elbows in D2 Pipework
Pipe SizeStandard 90Β° Elbow45Β° ElbowLong-Radius 90Β° BendTee (straight through)
22mm0.8m0.4m0.5m0.3m
28mm1.0m0.5m0.6m0.4m
35mm1.4m0.7m0.9m0.6m
42mm1.7m0.9m1.1m0.7m
Calculation method: Total equivalent length = actual straight pipe length + sum of all fitting equivalent lengths. If total equivalent length exceeds the maximum for the chosen D2 pipe size, you must either (a) increase D2 pipe size by one size, (b) reduce the number of bends, or (c) reduce the physical pipe run length.

Worked Equivalent Length Formula

L_equiv = L_straight + (n_90_elbows Γ— K_90) + (n_45_elbows Γ— K_45) + (n_LR_bends Γ— K_LR)

Where L_straight = measured pipe length in metres, n = number of each fitting type, K = equivalent length penalty from the table above.

D2 Discharge Pipe Sizing Tables β€” Full Reference

D2 Pipe Sizing β€” Approved Document G Reference Table (All Standard Sizes)
ScenarioD1 SizeD2 SizeMax Equiv. LengthMax 90Β° Elbows (std)Compliance
Short domestic run15mm22mm9.0m11 maxβœ“ Compliant
Medium domestic run15mm28mm18.0m18 maxβœ“ Compliant
Long domestic run15mm35mm27.0m19 maxβœ“ Compliant
Commercial short22mm28mm18.0m18 maxβœ“ Compliant
Commercial medium22mm35mm27.0m19 maxβœ“ Compliant
Undersized β€” common error15mm15mmN/AN/Aβœ— Non-compliant
Same size β€” not permitted22mm22mmN/AN/Aβœ— Non-compliant
Copper vs Plastic D2 Pipe β€” Hydraulic Performance Comparison
PropertyCopper (BS EN 1057)CPVC / HT PlasticStainless Steel
Max service tempβ‰₯ 95Β°C (unlimited)95Β°C (check mfr)β‰₯ 95Β°C
Permitted for D1βœ“ Yesβœ— Noβœ“ Yes
Permitted for D2βœ“ Yesβœ“ If approvedβœ“ Yes
Absolute roughness Ξ΅0.0015mm (smooth)0.0015mm (smooth)0.015–0.025mm
Bore equivalenceStandardStandardStandard
Freeze susceptibilityRisk in exposed runsRisk in exposed runsRisk in exposed runs
Max length (22mm)9.0m equivalent9.0m equivalent9.0m equivalent
Max length (28mm)18.0m equivalent18.0m equivalent18.0m equivalent

D2 Discharge Pipe Termination Requirements

The termination point of the D2 pipe is as important as its sizing. A correctly sized D2 pipe that terminates inappropriately remains non-compliant. Approved Document G sets out specific requirements for where and how D2 pipework must terminate.

Approved Termination Locations

βœ“ Trapped Gully (Preferred)
D2 discharges over a trapped gully at a visible, low-level external location. The pipe end must be above the gully grating but below the surface. This is the most common and recommended termination for domestic installations. Must be visible from inside the building.
βœ“ External Wall β€” Low Level
D2 exits through the external wall and discharges at low level (within 100mm of the ground or paved surface). Must have a visible air gap of at least 2Γ— pipe bore above any potential backfill level. A hooded termination fitting is required.
βœ“ Internal β€” Air Gap into Drain
Where external discharge is impractical, the D2 can discharge internally with a visible air gap over a trapped drain (minimum 20mm air break). The tundish or a secondary tundish acts as the visible indicator. Used in apartments and commercial buildings.
βœ— Not Permitted β€” Direct to Drain
D2 must never connect directly to a soil or waste pipe without an air gap. A direct pipe-to-drain connection removes the visible air break required by G3 and risks backflow contamination of the hot water system.
βœ— Not Permitted β€” Concealed Termination
The D2 termination must be in a visible location. Terminating in a void, ceiling space, or behind an access panel fails the G3 visibility requirement. If discharge occurs, it must be detectable by building occupants.
⚠ Caution β€” Frost Risk Locations
Where D2 passes through unheated spaces or exits externally, freeze protection is essential. A frozen D2 creates dangerous back-pressure against the relief valve. Insulate any pipe section exposed to temperatures below 5Β°C, and ensure the termination fitting cannot trap ice.

Termination Visibility Requirement

The G3 visibility requirement means the discharge point β€” whether the tundish in the airing cupboard or the D2 termination point externally β€” must be observable without using tools or moving fixed objects. The purpose is to alert occupants that a safety device has operated and that the system requires inspection by a competent engineer. Where the D2 runs a long distance, a secondary visible indicator (such as a sight glass or second tundish) can be used.

Worked Calculation Examples

Example 1: Standard 210L Domestic Cylinder β€” Short Run

Scenario: 210 litre unvented cylinder, 15mm TPRV outlet, tundish in airing cupboard, D2 runs 4.2m through ceiling void and exits through external wall. Two 90Β° standard elbows (22mm) in D2 run.

1

Determine D1 Size

TPRV outlet = 15mm. D1 pipe = 15mm copper. Length of D1 = 420mm (within 600mm limit). βœ“

2

Determine Minimum D2 Size

D1 is 15mm β†’ D2 minimum = 22mm (one size up). Start with 22mm D2.

3

Calculate Total Equivalent Length

Straight pipe: 4.2m 2Γ— 90Β° elbows: 2 Γ— 0.8m = 1.6m ───────────────────────────── Total equiv. length: 5.8m
4

Check Against Maximum

22mm D2 maximum equivalent length: 9.0m Calculated equivalent length: 5.8m Result: 5.8m < 9.0m β†’ βœ“ COMPLIANT
5

Verify Continuous Fall

D2 run must maintain minimum 1:200 fall (5mm per metre). Over 4.2m pipe run, minimum total fall = 21mm. Confirm with installer. Termination over trapped gully at external wall low level. βœ“

Example 2: Long D2 Run β€” Multiple Bends

Scenario: 300L commercial unvented cylinder, 15mm D1, D2 must run 12m through service corridor with four 90Β° standard elbows (28mm).

1

Start with 22mm D2 (minimum)

Straight: 12.0m + 4 elbows Γ— 0.8m = 12.0 + 3.2 = 15.2m 22mm maximum: 9.0m 15.2m > 9.0m β†’ βœ— FAIL at 22mm
2

Try 28mm D2

Straight: 12.0m + 4 Γ— 1.0m = 12.0 + 4.0 = 16.0m 28mm maximum: 18.0m 16.0m < 18.0m β†’ βœ“ COMPLIANT at 28mm
3

Final Specification

Use 28mm D2 copper pipe throughout. Verify 1:200 continuous fall (60mm over 12m). Terminate over trapped gully at visible, accessible external location.

Example 3: Plastic D2 Pipe β€” Apartment Installation

Scenario: 170L unvented cylinder in flat, 15mm D1, D2 must discharge internally into floor drain. 6.5m run, one 90Β° elbow, one 45Β° elbow (22mm fittings). Plastic pipe (manufacturer-approved, temperature rated).

1

Confirm Plastic is Acceptable

Check cylinder manufacturer's documentation β€” plastic (CPVC/HT-rated) approved for D2 in this model. D1 remains 15mm copper. βœ“

2

Calculate Equivalent Length at 22mm

Straight: 6.5m 1Γ— 90Β° elbow: 0.8m 1Γ— 45Β° elbow: 0.4m ───────────────── Total: 7.7m 22mm maximum: 9.0m 7.7m < 9.0m β†’ βœ“ COMPLIANT at 22mm
3

Termination

Discharge to floor drain with visible air gap (minimum 20mm above drain grating). Tundish in accessible airing cupboard acts as primary visible indicator. βœ“

Common D2 Discharge Pipe Installation Mistakes

These are the most frequently encountered non-compliant discharge pipe installations identified during G3 inspection and remedial surveys:

βœ— D2 Same Size as D1
Using 15mm D2 from a 15mm tundish outlet. The most common non-compliance. D2 must always be a minimum one pipe size larger. Replace immediately.
βœ— Exceeding Maximum Equivalent Length
Running 22mm D2 pipe over 9m equivalent length without upsizing to 28mm. Often caused by late routing changes during installation. Calculate before installing.
βœ— D2 Running Uphill
Any section of D2 pipe that rises against the direction of gravity creates a water trap and prevents complete gravity discharge. All D2 pipe must fall continuously at 1:200 minimum.
βœ— Tundish Concealed or Inaccessible
Installing the tundish behind a sealed panel or in a loft void fails the G3 visibility requirement. Tundish must be visible without tools. Non-notifiable defect during inspection.
βœ— D2 Direct-Connected to Drain
Connecting D2 directly to a soil pipe or waste pipe without an air gap removes the visible indicator and introduces risk of drain backflow into the system. Always maintain an air gap at discharge.
βœ— Plastic D1 Pipe
Using plastic push-fit or PEX for the D1 connection from the valve to the tundish. The temperature of direct valve discharge can reach 95Β°C+ and will damage or collapse plastic D1 pipe.
βœ— Exposed D2 Without Frost Protection
D2 running through unheated loft or externally without lagging. A frozen D2 prevents discharge, creates dangerous back-pressure on the relief valve, and may cause the valve to stick open or closed.
βœ— D1 Longer Than 600mm
D1 runs exceeding 600mm are non-compliant under Approved Document G. If the cylinder layout makes a short D1 difficult, a pressure reducing valve and repositioned tundish may be required.

Frequently Asked Questions β€” D1, D2 & G3 Regulations

What size should a D2 discharge pipe be?
D2 must be at least one pipe size larger than the D1 (tundish outlet). For a 15mm D1, the minimum D2 size is 22mm. The exact size also depends on total equivalent pipe length β€” including penalties for bends. A 22mm D2 is limited to 9m equivalent length. If your run is longer, you must upsize to 28mm (18m maximum) or 35mm (27m maximum).
What are the G3 discharge regulations?
Building Regulations Approved Document G, Section G3 requires all unvented hot water storage systems above 15 litres to be fitted with temperature and pressure relief devices that discharge safely. The discharge pipework must be sized, routed, and terminated per the guidance β€” D1 (metal, max 600mm, to tundish), then D2 (minimum one size larger, continuous fall, to visible safe termination). Installation must be notified to the local authority by a G3-qualified competent person.
What is the difference between D1 and D2 pipework?
D1 is the short metal pipe from the relief valve outlet to the tundish β€” maximum 600mm, metal only, vertical or near-vertical. D2 is the longer discharge pipe from the tundish to the final termination point β€” minimum one size larger than D1, must have continuous fall of 1:200, can be metal or approved high-temperature plastic, and must terminate in a visible location.
Can D2 discharge pipework be plastic?
Yes, provided the plastic is approved by the cylinder manufacturer and rated for sustained high-temperature service (95Β°C+). CPVC and some specialist thermoplastic systems are acceptable. However, D1 (from the relief valve to the tundish) must always be metal copper or stainless steel β€” plastic is never acceptable for D1 due to the extreme temperatures involved during a discharge event.
How long can a D2 discharge pipe be?
Maximum D2 length is expressed as equivalent length, which accounts for bends: 22mm D2 = maximum 9m equivalent; 28mm D2 = maximum 18m equivalent; 35mm D2 = maximum 27m equivalent. Each standard 22mm 90Β° elbow adds 0.8m equivalent; 28mm elbow adds 1.0m; 35mm elbow adds 1.4m. The actual physical run can be shorter than the equivalent length limit if bends are minimised.
Can D2 discharge pipework run uphill?
No. D2 must maintain a continuous fall of at least 1:200 (5mm drop per metre) throughout its entire length. Any section that rises β€” even briefly β€” will trap water after a discharge event, preventing the system from returning to a watertight condition and potentially causing corrosion. If the layout makes a gravity fall difficult, the installation location of the cylinder or the termination point must be revised.
Where can a D2 discharge pipe terminate?
Approved D2 termination options include: (1) over a trapped gully at external low level; (2) through an external wall with a visible hooded termination at low level; (3) with a visible air gap into an internal floor drain or trapped drain. The termination must always be visible to building occupants. Discharge must not be directed onto foot-traffic areas at high level (scalding risk) or into concealed voids.
Does D2 discharge pipe need insulation?
G3 does not mandate thermal insulation for D2 pipework, but freeze protection is critical where the pipe passes through unheated spaces (roof voids, garages) or exits the building. A frozen D2 prevents safe discharge and creates dangerous back-pressure on the relief valve. Any exposed sections should be lagged with frost-protection grade insulation and the termination fitting must allow drainage to prevent ice blockage.
What happens if the D2 discharge pipe is undersized?
An undersized D2 pipe creates back-pressure at the tundish outlet, which can prevent the relief valve from fully discharging or from closing properly after a discharge event. In severe cases, this can cause the system to remain at dangerously elevated temperature and pressure. Additionally, restricted discharge may cause water to overflow from the tundish (indicating a back-pressure condition) rather than flowing cleanly through the D2 β€” a clear sign of non-compliance requiring immediate remediation.
What is a tundish and why is it required?
A tundish is a funnel-shaped fitting that creates a visible air break between the D1 pipe (from the relief valve) and the D2 discharge pipe. It is required by G3 Building Regulations for two reasons: (1) it provides a visible indicator that a relief valve has operated, alerting occupants and engineers to a potential system fault; (2) the air break prevents back-pressure from the D2 system from acting against the relief valve, which could impair its operation. The tundish must be permanently accessible and visible without tools.

Anglian Plumbing Heating & Electrics β€” Gas Safe Registered Β· NAPIT Approved Β· G3 Qualified Engineers Β· Suffolk & Essex since 1998

All Engineering Calculators Β· Unvented Cylinder Services Β· Contact Us

Calculations based on Approved Document G (2016 Edition) and manufacturer guidance tables. Results are for guidance by qualified engineers. Always verify against current Building Regulations and manufacturer documentation. Β© 2025 AnglianPHE

Anglian P.H.E. Footer β€” Fully Responsive