Gas Pipe Sizing Calculator (UK)

Gas Pipe Sizing Calculator (UK)

Estimate the correct gas pipe diameter based on total appliance load and pipe length, following UK BS 6891 guidance.

Gas Pipe Size Recommendation

UK Guidance: Calculations are based on typical pressure drops in accordance with BS 6891. Always verify with manufacturer tables.
⚠️ Safety Notice: Gas pipework must only be designed and installed by Gas Safe registered engineers.
Β© 2025 Gas Pipe Sizing Calculator (UK)
Gas Pipe Sizing Calculator UK | Free Tool + Charts + Guide
πŸ”₯ Free UK Tool Β· BS 6891 Guidance

Gas Pipe Sizing Calculator UK

Instantly calculate the correct gas pipe size for any boiler, appliance or installation. Includes sizing charts, BS 6891 tables, formulas and a full step-by-step guide.

βœ“ Domestic & light commercial βœ“ Copper & steel pipe βœ“ kW & BTU sizing βœ“ Free to use

What Is Gas Pipe Sizing?

Gas pipe sizing is the process of choosing the right internal pipe diameter to deliver enough gas β€” at the right pressure β€” to every appliance in a property. Get it right and your boiler, cooker and fires all work perfectly. Get it wrong and you risk pressure drops, appliance lockouts, and serious safety problems.

In the UK, natural gas systems typically operate at a supply pressure of 21 mbar. Under BS 6891 (the standard for low-pressure gas pipework), the maximum allowable pressure drop between the meter and any appliance is just 1 mbar. That tiny margin means pipe diameter, pipe length and total gas demand must all be calculated carefully.

This page gives you everything you need: a free gas pipe sizing calculator, UK sizing charts, the sizing formula explained simply, a worked example, common mistakes to avoid and a full FAQ.

πŸ”’

Safety

Undersized pipes can starve appliances of gas, create pressure fluctuations and increase the risk of incomplete combustion.

⚑

Efficiency

Correctly sized gas pipework ensures appliances run at their rated output, reducing fuel waste and energy bills.

πŸ“‹

Compliance

UK gas installations must comply with Gas Safety (Installation and Use) Regulations and BS 6891. Correct sizing is a legal requirement.

Gas Pipe Sizing Calculator (UK)

Enter your total appliance load and pipe run details. Results follow BS 6891 / IGE/UP/2 guidance.

β€”
Recommended Pipe Diameter (OD)
⚠️ Important: This calculator provides guidance only. All gas pipework must be designed and installed by a Gas Safe registered engineer in accordance with BS 6891 and the Gas Safety (Installation and Use) Regulations.

How to Use the Gas Pipe Sizing Calculator

The calculator needs four inputs:

  • Total Gas Load (kW): Add up the kW ratings of all appliances the pipe run must supply. For a single 24 kW combi boiler, enter 24. For a boiler plus a gas hob (10 kW), enter 34.
  • Pipe Length (m): Measure the total run from your gas meter to the farthest appliance β€” not just the straight-line distance. Include all bends and tees.
  • Pipe Material: Copper has a slightly higher flow resistance than steel of the same nominal diameter. Select the material you plan to use.
  • Number of Fittings / Bends: Each elbow, tee or valve adds equivalent pipe length. The calculator converts these to an equivalent extra pipe length automatically.

The output is the minimum recommended outside diameter (OD) in millimetres, based on a maximum 1 mbar pressure drop at 21 mbar supply pressure.

Gas Pipe Sizing Chart UK

The tables below show the maximum gas load (kW) that each standard pipe size can carry at different pipe lengths, following UK BS 6891 guidance for natural gas at 21 mbar supply pressure and a 1 mbar maximum pressure drop. Use these alongside the gas pipe size calculator to verify your selection.

Gas Pipe Sizing Chart β€” kW Capacity by Pipe Diameter & Length (Copper, UK)

Pipe OD Internal Ø (approx) 3 m run 6 m run 10 m run 15 m run 20 m run 30 m run
15 mm13.6 mm28 kW19 kW14 kW11 kW9 kW7 kW
22 mm19.6 mm87 kW60 kW45 kW36 kW30 kW23 kW
28 mm25.6 mm180 kW126 kW95 kW75 kW63 kW48 kW
35 mm32.0 mm340 kW240 kW180 kW142 kW120 kW92 kW
42 mm38.8 mm580 kW410 kW306 kW243 kW204 kW157 kW

Values are indicative for Type R250 copper tube (EN 1057) at 21 mbar supply, 1 mbar max drop, natural gas calorific value 38.6 MJ/mΒ³. For precise design, consult manufacturer tables or a Gas Safe engineer.

Gas Pipe Sizing Chart β€” kW to Pipe Diameter Quick Reference

Appliance Load Short Run (< 6 m) Medium Run (6–15 m) Long Run (> 15 m) Typical Use Case
Up to 15 kW15 mm βœ“15 mm22 mmSmall gas fire, tumble dryer
16–25 kW15 mm22 mm Rec.22 mm24 kW combi boiler
26–35 kW22 mm22 mm Rec.28 mm30–35 kW system boiler
36–50 kW22 mm28 mm Rec.28 mmBoiler + hob + fire
51–80 kW28 mm28 mm35 mm Rec.Large house, multiple appliances
81–120 kW35 mm35 mm42 mmLight commercial
121 kW+Specialist design required β€” IGE/UP/2 Edition 3Commercial / industrial

Gas Pipe Sizing Chart β€” BTU Capacity (for older appliance specs)

Pipe OD 10 ft (3 m) 20 ft (6 m) 50 ft (15 m) 100 ft (30 m)
15 mm95,400 BTU64,800 BTU37,500 BTU24,000 BTU
22 mm297,000 BTU205,000 BTU123,000 BTU78,000 BTU
28 mm615,000 BTU430,000 BTU257,000 BTU164,000 BTU
35 mm1,160,000 BTU820,000 BTU485,000 BTU314,000 BTU

1 kW β‰ˆ 3,412 BTU/hr. BTU values rounded for practical use.

Standard Gas Pipe Sizes in the UK

UK domestic and light commercial gas systems use metric copper or steel pipe. Here are the standard gas pipe sizes and where each is typically used.

15mm
OD / ~13.6mm ID
Short individual appliance spurs. Gas fires, tumble dryers, cooker connections. Not suitable for boilers on runs over 6 m.
22mm
OD / ~19.6mm ID
The most common domestic gas pipe size. Suitable for most combi boilers (up to ~35 kW) on runs up to 15 m.
28mm
OD / ~25.6mm ID
Larger homes with multiple appliances or long pipe runs. Used as the main feed from meter to manifold in busy systems.
35mm
OD / ~32mm ID
High-demand domestic or light commercial. Multi-apartment feeds, large system boilers, commercial kitchens.
42mm+
OD / ~38.8mm ID
Commercial and industrial installations. Requires specialist IGE/UP/2 design. Must be installed and commissioned by a Gas Safe engineer.

Copper vs Steel Gas Pipe

FeatureCopper PipeSteel / Black Iron Pipe
Standard (UK)EN 1057, Type R250BS EN 10255
Common sizes15, 22, 28, 35, 42 mm ODDN15, DN20, DN25, DN32, DN40
Typical useDomestic, residential, small commercialCommercial, industrial, high-pressure runs
Flow resistanceSlightly higher (smooth bore)Lower internal roughness when new
CorrosionExcellent resistanceRequires protection / coatings externally
JointingSolder, compression, press-fitThreaded, flanged, welded
CostModerateLower per metre but higher labour
Note on CSST (Corrugated Stainless Steel Tubing): CSST (e.g. TracPipe, OmegaFlex) is increasingly used in UK installations for flexible routing. It has different flow characteristics and must be sized using the manufacturer's own sizing tables. Always follow the manufacturer's guidance and Gas Safe requirements.

Gas Pipe Sizing Formula Explained

You don't need to use the formula manually β€” the calculator above does it for you. But understanding the logic helps you make better decisions and spot potential problems.

The Core Idea: Flow Rate and Pressure Drop

A gas pipe must deliver a high enough volumetric flow rate (measured in mΒ³/h) to meet the total appliance demand, without losing too much pressure along the way.

The key relationship is this: the longer or narrower the pipe, the more resistance it creates, and the more pressure you lose before the gas reaches the appliance.

Step 1 β€” Convert kW to flow rate
Q = P Γ· CV
  • Q = volumetric flow rate (mΒ³/h)
  • P = total appliance load (kW)
  • CV = calorific value of natural gas β‰ˆ 10.73 kWh/mΒ³ (gross)
Step 2 β€” Pressure drop (simplified Weymouth formula)
Ξ”P = (C Γ— L Γ— QΒ²) Γ· D⁡
  • Ξ”P = pressure drop (mbar)
  • C = friction factor constant (depends on gas, pipe material)
  • L = equivalent pipe length (m) β€” including fittings allowance
  • Q = flow rate (mΒ³/h)
  • D = internal pipe diameter (mm)

In practice, Gas Safe engineers use manufacturer sizing tables (published by British Gas / Transco) or software tools rather than calculating this by hand. The maximum permitted pressure drop for domestic gas pipework under BS 6891 is 1 mbar.

Equivalent Pipe Length (Fittings Allowance)

Every elbow, tee or valve creates turbulence and adds resistance. Engineers convert these to an "equivalent pipe length" β€” extra metres added to the measured pipe run before looking up sizing tables.

Fitting Type15 mm equiv.22 mm equiv.28 mm equiv.
90Β° elbow0.5 m0.8 m1.0 m
Equal tee (flow through branch)1.5 m2.0 m2.5 m
Ball valve / isolating cock0.3 m0.5 m0.6 m
45Β° elbow0.3 m0.5 m0.6 m
Meter / regulatorTypically 3–5 m equivalent β€” check manufacturer data

Step-by-Step Example: Sizing Gas Pipe for a 24 kW Combi Boiler

This is the most common scenario in UK domestic gas work. Here's exactly how to calculate the correct gas pipe size for a 24 kW combi boiler with a 10 m pipe run.

1

List all appliances on the same pipe run

In this example: one 24 kW combi boiler. If there were also a gas hob (10 kW) and a gas fire (5 kW), the total would be 39 kW. Here, total load = 24 kW.

2

Measure the pipe run from meter to boiler

Measure along the actual pipe route β€” not a straight line. In this example the measured run is 8 m, with 4 elbows. Each elbow on 22 mm pipe = 0.8 m equivalent. So: 8 + (4 Γ— 0.8) = 11.2 m equivalent pipe length.

3

Convert kW to volumetric flow rate

Q = 24 kW Γ· 10.73 kWh/mΒ³ = 2.24 mΒ³/h. This is the gas flow your pipe must deliver.

4

Look up the gas pipe sizing chart

Using the BS 6891 / Transco table for copper pipe, 21 mbar supply, 1 mbar max drop: at 11.2 m equivalent length and 24 kW demand β€” 22 mm OD copper pipe is sufficient. The table shows 22 mm can carry up to 45 kW at 10 m, well above our 24 kW requirement.

5

Check the meter outlet size

Most UK domestic gas meters have a 22 mm outlet connection. If upgrading to a larger boiler or adding appliances, check the meter outlet capacity and contact Cadent / SGN if an upgrade is needed.

6

Final answer

22 mm OD copper pipe is the correct gas pipe size for a 24 kW combi boiler on a 10 m run in this scenario. If the run were longer than 20 m, 28 mm would be required.

Gas Pipe Size for Common UK Boilers

Boiler OutputRun < 6 mRun 6–15 mRun 15–25 mRun > 25 m
24 kW combi boiler15 mm22 mm Rec.22 mm28 mm
28 kW combi boiler22 mm22 mm Rec.22 mm28 mm
30 kW combi boiler22 mm22 mm28 mm Rec.28 mm
35 kW system boiler22 mm22 mm28 mm Rec.28 mm
40 kW system boiler22 mm28 mm Rec.28 mm35 mm
Boiler + hob + fire (~45 kW)28 mm28 mm Rec.28 mm35 mm

These recommendations assume a single straight pipe run from the meter to the appliance. Always verify against the manufacturer's commissioning data and the actual site layout.

Common Gas Pipe Sizing Mistakes

These are the errors that cause most gas pressure and performance problems in UK properties. Knowing them helps you avoid costly re-work or safety issues.

πŸ”»

Using 15 mm pipe for a modern boiler

A 15 mm pipe can only carry around 14 kW at a 10 m run. Most modern combi boilers are 24–35 kW. A 15 mm supply almost guarantees pressure drop problems, especially when the boiler fires at full output.

πŸ“

Not measuring the actual pipe route

Sizing based on a straight-line estimate instead of the real pipe route β€” including drops through floors, bends around joists and tees to other appliances β€” results in seriously undersized pipe.

πŸ”§

Forgetting fittings in the equivalent length

Each elbow or tee adds equivalent pipe resistance. On a run with 8 elbows, forgetting to add the equivalent length can undersize the pipe by the equivalent of 6+ extra metres.

βž•

Sizing for one appliance, not all of them

When multiple appliances share a pipe section, the pipe must carry the combined gas demand. Sizing only for the boiler and ignoring a gas hob or fire on the same run is a very common mistake.

πŸ“‰

Ignoring meter outlet capacity

The UK domestic gas meter and its outlet are typically rated for a maximum flow. Adding a large new boiler or multiple appliances without checking meter capacity can restrict the entire system, regardless of pipe size.

πŸ”„

Not upgrading legacy 15 mm pipework

Many older UK properties still have 15 mm gas pipes installed for previous appliances with lower outputs. Simply swapping to a modern high-output boiler without upgrading the gas pipe is a frequent cause of boiler lockouts and poor performance.

Frequently Asked Questions

To calculate gas pipe size, you need to know three things: (1) the total gas demand in kW of all appliances on that pipe run, (2) the total equivalent pipe length in metres (measured route plus an allowance for fittings), and (3) the pipe material (copper or steel). Convert the kW demand to a volumetric flow rate (mΒ³/h) by dividing by 10.73. Then look up the appropriate pipe diameter from a BS 6891 sizing table, or use a gas pipe sizing calculator like the one at the top of this page. The pipe you choose must carry the required flow with no more than 1 mbar pressure drop at 21 mbar supply pressure.

For most UK domestic combi boilers (24–35 kW) on pipe runs up to 15 m, 22 mm OD copper pipe is the standard recommendation. For runs longer than 20 m, or where multiple appliances share the same pipe section, 28 mm is usually required. A 15 mm pipe is generally too small for modern boilers on anything other than the very shortest spur connections (under 3 m). Always check against the boiler manufacturer's gas supply requirements in the installation manual.

Gas pipe sizing involves four steps: (1) list all appliances supplied by that pipe section and add their kW ratings together; (2) measure the pipe route carefully and add equivalent lengths for fittings (elbows, tees, valves); (3) convert the total kW to a flow rate in mΒ³/h; (4) look up the minimum pipe diameter in the BS 6891 / Transco sizing tables that delivers that flow at your required equivalent length. The gas pipe sizing calculator on this page automates steps 3 and 4 for you.

Gas pipe size is determined by two main factors: the total gas demand (kW) that the pipe must supply, and the total equivalent pipe length. Longer runs and higher demands both require larger diameters to keep pressure drop within the 1 mbar limit specified by BS 6891. You use a gas pipe sizing calculator or published Transco sizing tables to find the minimum acceptable diameter. Always round up to the next standard pipe size β€” never down.

In the UK, copper gas pipe is measured and sold by outside diameter (OD). So "22 mm pipe" means the outside is 22 mm across. To measure an existing pipe, use a set of pipe ID/OD callipers or wrap a string around the pipe and measure the circumference, then divide by Ο€ (3.14159) to get the OD. Do not confuse OD with ID (internal diameter) β€” the internal diameter of 22 mm copper pipe is approximately 19.6 mm. Steel pipe is described differently using DN (nominal bore) sizes; DN20 steel pipe is broadly equivalent in capacity to 22 mm copper.

An undersized gas pipe creates excessive pressure drop. At the appliance end, the gas pressure falls below what the appliance needs to operate correctly. For a boiler, this typically causes: failure to ignite at full output, the boiler locking out on a low-gas-pressure fault, intermittent operation (especially when other appliances are also on), and incomplete combustion in severe cases. An undersized gas line can also cause a boiler to run at reduced output, raising energy bills and shortening appliance life.

Only on a very short spur of 3 m or less. At 10 m, 15 mm copper pipe can only carry around 14 kW β€” well below the 24 kW demand of the boiler. In practice, most Gas Safe engineers will specify 22 mm as the minimum for any combi boiler connection, even on short runs, to give adequate capacity margin and comply with manufacturer requirements. Using 15 mm pipe for a modern high-output boiler on a standard domestic pipe run will almost certainly cause pressure drop problems.

The most common standard gas pipe sizes in UK domestic properties are 15 mm, 22 mm and 28 mm OD copper tube (to EN 1057). 22 mm is the most widely used size, suitable for most combi boiler installations. 15 mm is used for short spurs to individual appliances. 28 mm is used for the main meter-to-distribution run in properties with multiple gas appliances or longer pipe routes. 35 mm and 42 mm are used in larger domestic or light commercial settings.

The gas pipe sizing formula is based on the Weymouth equation for compressible flow: Ξ”P = (C Γ— L Γ— QΒ²) Γ· D⁡, where Ξ”P is pressure drop in mbar, L is equivalent pipe length in metres, Q is flow rate in mΒ³/h, D is internal pipe diameter in mm, and C is a constant that depends on gas type and pipe material. In practice, engineers use published BS 6891 sizing tables (based on this formula) or software tools rather than calculating this by hand. The target is always Ξ”P ≀ 1 mbar for domestic gas.

Yes. If a gas pipe is too small, the boiler cannot receive enough gas at the correct pressure to fire at full rated output. This means the boiler modulates down or locks out, reducing efficiency and increasing run times. On the other hand, correctly sized gas pipework ensures the boiler gets a stable gas supply at 20–21 mbar, allowing it to run at peak efficiency. This is particularly important for condensing boilers, which need stable operation to reach their rated seasonal efficiency.

Disclaimer: The gas pipe sizing calculator and tables on this page provide general guidance only, based on BS 6891 principles for low-pressure natural gas systems in the UK. Results should always be verified against the current edition of BS 6891, IGE/UP/2, and the appliance manufacturer's installation instructions. All gas pipework must be designed, installed, tested and commissioned by a Gas Safe registered engineer in compliance with the Gas Safety (Installation and Use) Regulations 1998 (as amended). Anglian P.H.E. accepts no liability for decisions made based solely on this calculator.
Anglian P.H.E. Footer β€” Fully Responsive